XZH TEST completed a 10kV power cable fault detection project for an industrial client, combining low-voltage pulse and high-voltage flashover methods to locate a main-insulation fault on a cable 1038.88 metres long. The fault was pinpointed 345.72 metres from the test end, and the findings point to a likely problem at an intermediate joint. The following is the full test report summary.
Project Particulars| Project | 10kV cable fault detection for an industrial client |
| Test personnel | Ye Peng, Ge Haojie |
| Test date | 11 September 2026 |
| Cable model | 8.7/10kV |
| Site information | From the substation to the plant area, laid through conduits and trenches; Phase A insulation measured 3.2 MΩ |
| Instruments used | 5/50 operating-box test transformer, 40/6 capacitor, 503E+ pinpoint locator, cable identification instrument, 501A main unit, and burn-through (burn-out) set |
| Fault nature | Megger test: Phase A 3.2 MΩ at 2489 V; the other phases were normal |
| Cable length | Total length 1038.88 m |
The rough fault distance was measured using the low-voltage pulse method and the high-voltage flashover method. A high-voltage impulse flashover waveform was captured, and the fault point was found to be 345.72 m from the test end.
Waveform AnalysisThe captured waveforms were analysed as follows:
With the voltage raised to about 22 kV, the search proceeded along the cable route, and the discharge sound of the fault point was heard at about 345.72 m from the test end, confirming the fault location.
Test SummaryContact XZH TEST for cable fault detection equipment and on-site technical support.